5.12 Primary head
Please refer to Sect. 3.2 “factory settings”
Fct. 3.02 FLOW METER
Press
key.
DIAMETER = set meter size (see instrument nameplate)
press
key
Select size from table of meter sizes:
DN 2.5 - 1000 mm equivalent to
1
/10 - 40 inch
Select using
key.
Transfer to subfunction “FULL SCALE”
with
key.
FULL SCALE = set full-scale range,
press
key.
Set as described in Sect. 5.1.
Transfer to subfunction “GK VALUE” with
key.
Note: if “VALUE P” is displayed after pressing key.
PULSE/VOL. is set under Fct. 1.06 PULS B1, subfunction “SELECT P”. Because the full-scale
range Q
100%
has been changed, the output frequency (F) of the pulse output is over- or
undershot: P
min
= F
min
/ Q
100%
P
max
= F
max
/ Q
100%
Change pulse value accordingly, see Sect. 5.7 pulse output B1, Fct. 1.06.
GK VALUE = set primary constant GK,
press
key.
1.0000 - 9.9999 (note information on instrument nameplate, do not change setting !)
Change flashing digit (cursor) with
key.
Shift cursor 1 place to right or left with
key.
Transfer to subfunction “FIELD
FREQ.” with
key.
FIELD FREQ. = set magnetic field frequency,
press
key
1/2 • 1/6 (1/2, 1/6, 1/18 and 1/36 of power frequency, see instrument nameplate,
1/18 • 1/36 do not change setting, exce
ptions see Sect. 6.4-6.6 !)
Select using
key.
Transfer to subfunction “FLOW DIR.”
with
key.
(only for units with DC power supply, transfer to subfunction “LINE FREQ”).
LINE FREQ. = normal line frequency in your country,
press
key.
50 Hz
Select using the
key.
60 Hz
Transfer to subfunction “FLOW DIR.” with key.
FLOW DIR. = set flow direction,
press
key.
+ DIR. (for identification of flow direction, see “+” arrow on primary head;
- DIR. for F/R mode, identifies the “positive” flow direction)
Select using the
key.
Press
key to return to Fct. 3.02 FLOW METER.
Zero check, see Fct. 3.03 and Sect. 7.1.