5/4
Current output I 5.6
Fct. 1.05 CURRENT I
Press
key.
FUNCT. I = Select function for current output,
press
key
OFF (switched off, no function)
1 DIR. (1 flow direction)
2 DIR. (2 flow directions, F/R mode, forward/reverse)
Select using
key.
Transfer to subfunction “RANGE I”
with
key.
Exceptions: When “OFF” selected, return to Fct. 1.05 CURRENT I.
When “2 DIR.”selected, transfer to subfunction
“REV.RANGE”.
REV.RANGE = define full-scale range for reverse flow
(appears only when “2 DIR.” set under “FUNCT. I” above)
Press
key
100 PCT. (same full-scale value Q
100%
as forward flow, see Fct. 1.01)
PERCENT (settable range) Settin
g range 005 – 150% of Q100% (see Fct. 1.01)
Select with
key.
Press
key to transfer to number setting.
Press
key to transfer to subfunction “RANGE I”.
RANGE I = select measuring range,
press
key
0 - 20 mA
fixed ranges
4 - 20 mA
mA (user-defined value) I
0%
– I
100%
(value I
0%
< I
100%
!) 0-16 mA 4-20 mA
Press
key to transfer to number setting.
Select with key
.
Press key
to transfer to subfunction “I ERROR”.
I ERROR = set error value,
press
key
22 mA (fixed value)
0.0 - I
0%
mA (variable value; only variable when I
0%
1 mA, see ”RANGE I“ above)
Select using key
. Press
key to transfer to number setting.
Press key
to return to Fct. 1.05 CURRENT I.
Please refer to Sect. 3.2 “Factory settings”.
Refer to Sect. 2.6 for connection diagrams, and to Sect. 5.15 for characteristics.
}