ADCP-80-570 • Issue 2 • March 2006
Page 11
© 2006, ADC Telecommunications, Inc.
1.23 Dimensions
Dimens io ns
Figure 6. Panel Dimensions
Torque
Mounting bracket chassis screws 15 pound-force inches 1.7 Newton meters
Mounting bracket rack screws 27 pound-force inches 3.1 Newton meters
Alarm contacts 9 pound-force-inches 1 Newton meter
Input power terminal nuts 32 pound-force inches max. 3.5 Newton meters max.
Output power terminal screws 12 pound-force inches max. 1.3 Newton meters max.
Grounding stud nuts 20 pound-force inches max. 2.2 Newton meters max.
Table 2. Circuit Breaker Panel Specifications, continued
PARAMETER SPECIFICATION REMARKS
17.13 IN.
(43.5 CM)
23.00 IN.
(58.4 CM)
22.31 IN.
(56.7 CM)
11.10 IN.
(28.2 CM)
10.00 IN.
(25.4CM)
1.75 IN.
(4.4 CM)
1.12 IN.
(2.9 CM)